Back to the archive
Public document · Water

2025 Smiths Falls Drinking Water System Annual Report

Public source material preserved in the Field Guide. Consult the original for authoritative wording and current status.

Source text

TOWN OF SMITHS FALLS

S

SMITHS FALLS RISE AT THE FALLS

SMITHS FALLS DRINKING WATER SYSTEM

2025 ANNUAL REPORT Revision 1


Smiths Falls Drinking Water System <u><strong>2025 Annual Report</strong></u>

Drinking-Water System Number: Drinking-Water System Name: Drinking-Water System Owner: Drinking-Water System Category: Period being reported:220001307
Drinking-Water System Number: Drinking-Water System Name: Drinking-Water System Owner: Drinking-Water System Category: Period being reported:Smiths Falls Drinking Water System
Drinking-Water System Number: Drinking-Water System Name: Drinking-Water System Owner: Drinking-Water System Category: Period being reported:Corporation of the Town of Smiths Falls
Drinking-Water System Number: Drinking-Water System Name: Drinking-Water System Owner: Drinking-Water System Category: Period being reported:Large Municipal Drinking Water System
Drinking-Water System Number: Drinking-Water System Name: Drinking-Water System Owner: Drinking-Water System Category: Period being reported:January 1st to December 31st, 2025
Complete if your Category is LargeMunicipal Residential or Small MunicipalResidentialDoes your Drinking-Water System serve more than 10,000 people?Yes [ ] No [✓]Is your annual report available to the public at no charge on a web site on the Internet?Yes [✓] No [ ]Location where Annual Report required under O. Reg. 170/03 Schedule 11 will be available to the public.www.smithsfalls.caSmiths Falls Town Hall Complex77 Beckwith St. NSmiths Falls, ON K7A 4T6Complete for all other Categories.Number of Designated Facilities served: N/ADid you provide a copy of your annual report to all Designated Facilities you serve? N/ANumber of Interested Authorities you report to: N/ADid you provide a copy of your annual report to all Interested Authorities you report to for each Designated Facility? N/A

List all Drinking-Water Systems (if any), which receive all of their drinking water from your system:

Drinking Water System NameDrinking Water System Number
Atironto Subdivision – Montague Township260006828

Did you provide a copy of your annual report to all Drinking-Water System owners that are connected to you and to whom you provide all of its drinking water?

Yes [✓] No [ ]

Indicate how you notified system users that your annual report is available, and is free of charge.

[✓] Public access/notice via the web
[ ] Public access/notice via a newspaper


Smiths Falls Drinking Water System 2025 Annual Report

Describe your Drinking-Water System

The Smiths Falls Drinking Water System is comprised of the Water Treatment Plant (WTP) and Water Distribution System (WDS) which together provides a supply of potable water to the residents and businesses of the Town of Smiths Falls.

The WTP is a Class IV high-rate dissolved air floatation (AquaDAF ®) surface water plant having an approved design capacity of 14,000 m<sup>3</sup>/d with a future expansion to 18,000 m<sup>3</sup>/d. Raw water for the treatment process is drawn from the Rideau River (surface water). The intake structure is located upstream of the WTP approximately 170m. The intake consists of a concrete structure and a 762-millimeter diameter concrete pipe connecting the intake to the diversion chamber where the raw water is directed into the WTP.

Low lift pumps supply water to the AquaDAF ® which is a high-rate dissolved air floatation clarifier. A coagulant & polymer are mixed with Raw Water to aid in particle removal. Dissolved air will float these particles to form a blanket of sludge which is discharged to the wastewater collection system.

Clarified water flows to 3 granular activate carbon (GAC) & sand filters where further particle removal will take place.

Processes involved include UV disinfection; chlorination with chlorine gas; corrosion control; fluoridation; chlorine dioxide, residue management and de-chlorination.

The WDS was a Class I subsystem which was upgraded to Class II subsystem in September 2025 after submission and review of an application to the Ministry. This was due to a new 5,050 cubic meters (m<sup>3</sup>) water tower being constructed and commissioned in late 2025. The WDS consists of 61.94 kilometers (km) of mains, 834 valves, 399 hydrants, 3,226 residential services, and 300 commercial services. The old water tower that had a storage of 945 cubic meters (m<sup>3</sup>) was taken out of service in December 2025 and replaced with the new tower at 12 Air Care Dr.

List all water treatment chemicals used over this reporting period

CHEMICAL NAMEUSESUPPLIER
PAX-XL6CoagulantKemira
Norfloc 122PolymerNorthland Chemical
Chlorine GasDisinfectionBrenntag
Sodium HydroxideCorrosion ControlBrenntag
Fluorosilicic AcidFluoridePVS Benson
Calcium ThiosulfateDe-chlorinationCleartech
Sodium ChloritePre-treatment Zebra MusselPVS Benson

Were any significant expenses incurred to?

[✓] Install required equipment

[✓] Repair required equipment

[ ] Replace required equipment

Please provide a brief description and a breakdown of monetary expenses incurred

S Water Tower – $4,279,406.00

S Trunk Main For Water Tower (Engineering) - $22,477.82

S SCADA WTP – $18,914.00

S Parks Canada Water Service - $41,636.00

S Total Chlorine Analyzer (AIT 186) - $9,541.00

S Dissolved Air Flotation System Parts - $5,646.00

S High Lift Pump VFD Upgrade (HLP 184) - $65,679.50

S Watts Backflow Test Kit - $2,823.84

S George St Phase 2 (Water) - $488,845.00

S New MSA SCBA x2 with masks - $18,525.38

S Water Meter Replacement Program - $719,363.79

Provide details on the notices submitted in accordance with subsection 18(1) of the Safe Drinking Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to Spills Action Centre

Incident Date (YYYY-MM-DD)ParameterResultUnit of MeasureCorrective ActionCorrective Action Date (YYYY-MM-DD)
2025-02-05Fluoride1.70mg/LRe-sample for fluoride, re-sample result was 0.10mg/L2025-02-13
2025-04-14Chlorine (Free)0.03mg/LInitial sample at Town Hall was below the limit, flushed sample location for 5 minutes, re-tested after flush, result was 1.50 mg/L, Distribution flushed hydrants upstream and downstream. Regular bacti sample day2025-04-17
1-PLDU53Elevated Water Tower Leak (Old Mill)Leak spraying on grass and bit of pavement but not going to catch basins or the river. Leak was temporarily patched using a gasket and steel plate and ratchet straps. New Elevated Water Tower (Air Care Drive) is construction is progress with commission expected to take place end of December 2025.

Smiths Falls Drinking Water System <u><strong>2025 Annual Report</strong></u>

Microbiological testing completed under Schedule 10, 11 or 12 of Regulation 170/03 during this reporting period.

Number of SamplesRange of E. coli Results (min #) - (max #) (CFU/100mL)Range of Total Coliform Results (min #) - (max #) (CFU/100mL)Number of HPC SamplesRange of HPC Results (min #) - (max #) (CFU/100mL)
Raw520 - 4310 - 600N/AN/A
Treated520 - 00 - 052<10 - 210
Distribution - Routine3100 - 00 - 0310<10 - 1230
Distribution Water main Repairs/new installations/service repairs560 - 00 - 049<10 - 10

Operational testing completed under Schedule 7, 8 or 9 of Regulation 170/03 during the period covered by this Annual Report.

Parameter Tested - (Online Analyzers)Number of Grab SamplesRange of Results MinimumRange of Results AverageRange of Results Maximum
Turbidity - Raw Water (NTU) AIT 102Continuous Monitoring10.0000.88238.030
Turbidity - Raw Water (NTU) - DWSP(365 bench test)0.1240.9364.99
Turbidity - Raw Water (NTU) - River(54 bench test)0.5281.1134.36
Turbidity - Filter #1 (NTU) AIT 111Continuous Monitoring20.0000.0292.602
Turbidity - Filter #1 (NTU)(52 bench test)0.0420.0950.196
Turbidity - Filter #2 (NTU) AIT 121Continuous Monitoring20.0000.0321.299
Turbidity - Filter #2 (NTU)(53 bench test)0.0390.0950.197
Turbidity - Filter #3 (NTU) AIT 131Continuous Monitoring20.0000.0285.000
Turbidity - Filter #3 (NTU)(53 bench test)0.0430.1040.248
Turbidity - Finished Water (NTU) AIT 184Continuous Monitoring30.0000.0704.683
Turbidity - Finished Water (NTU)(245 bench test)0.0500.1110.240
Chlorine Free - Pre-Reservoir (mg/L) AIT 165Continuous Monitoring5 Free Chlorine0.002.515.00
Chlorine Free - Pre-Reservoir (mg/L)(53 bench test)1.202.393.07
Chlorine Free - Post Reservoir (mg/L) AIT 180Continuous Monitoring5 Free Chlorine0.001.745.00
Chlorine Free - Post Reservoir (mg/L)(53 bench test)1.261.692.03
Chlorine Free - Finished Water (mg/L) AIT 185Continuous Monitoring5 Free Chlorine0.001.805.00
Chlorine Free - Finished Water (mg/L)(248 bench test)1.161.772.38
Chlorine Total - Finished Water (mg/L) AIT 186Continuous Monitoring6 Total Chlorine0.002.114.58
Chlorine Total - Finished Water (mg/L)(246 bench test)1.092.042.68
Fluoride - Finished Water (mg/L) AIT 187Continuous Monitoring40.000.681.59
Fluoride - Finished Water (mg/L)(365 bench test)0.400.650.98
UV Transmittance (%) AIT 160Continuous Monitoring770.095.3100.0
UV Transmittance (%)(234 bench test)81.189.594.5

Smiths Falls Drinking Water System 2025 Annual Report

Notes for above table operational testing completed under Schedule 7, 8 or 9:

  1. High raw water turbidity spikes occur when the low lift pumps (LLP) start and stop, maintenance, calibration and flushing of lines.

  2. High filter turbidity results of filter backwash, process upset or calibration.

  3. High finished water turbidity results of high lift pumps (HLP) starting or calibration.

  4. High fluoride readings occur on HLP starts, maintenance or calibration while chemical system was off.

  5. Low free chlorine residual (pre-reservoir, post reservoir and finished water) result of generator backup power testing, maintenance or calibration.

  6. Low total chlorine residual (finished water) result of generator backup power testing, maintenance or calibration.

  7. Low UV transmittance result of generator backup power testing, maintenance, calibration or Optiview failure.

Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument.

Date of legal instrument issuedParameterDate Sampled (YYYY-MM-DD)Result (μ g/L)Quarterly Average (μ g/L)Rolling Annual Average Quarter (μ g/L)
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-01-0164.051.076.5
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-02-0343.051.076.5
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-03-0346.051.076.5
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-04-0748.069.374.8
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-05-0583.069.374.8
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-06-0277.069.374.8
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-07-07104.0101.373.2
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-08-05120.0101.373.2
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-09-0280.0101.373.2
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-10-0657.048.067.4
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-11-0347.048.067.4
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2025-12-0140.048.067.4

Notes:

  1. Maximum Allowable Concentration (MAC) for THM is based on a four-quarter rolling annual average of 0.100 mg/L or 100.0 ug/L
Date of legal instrument issuedParameterDate Sampled (YYYY-MM-DD)Result -Monthly TSS Average (mg/L)Result -Monthly Grab Average Total Chlorine (mg/L)
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-01-196.630.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-02-282.300.01
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-03-132.030.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-04-162.120.03
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-05-141.950.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-06-173.600.03
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-07-235.500.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-08-295.040.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-09-185.420.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-10-274.710.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-11-124.340.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2025-12-202.560.01
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)Annual average3.850.02

Smiths Falls Drinking Water System <u><strong>2025 Annual Report</strong></u>

Date of legal instrument issuedParameterSample Date (YYYY-MM-DD)Result Value (mg/L)Exceedance
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorite2025-02-030.09No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorite2025-05-050.05No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorite2025-08-05<0.01No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorite2025-11-03<0.01No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorate2025-02-030.15No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorate2025-05-050.07No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorate2025-08-050.08No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorate2025-11-030.08No

Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument.

Date of legal instrument issuedParameterSample Date (YYYY-MM-DD)Result Value (μ g/L)Exceedance
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 6)Microcystin2025-06-04<0.1No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 6)Microcystin2025-07-09<0.1No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 6)Microcystin2025-08-08<0.1No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 6)Microcystin2025-09-04<0.1No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 6)Microcystin2025-10-09<0.1No

Summary of Inorganic parameters tested during this reporting period or the most recent sample results Parameter Sample Date Result Value Unit of Exceedance

ParameterSample Date (YYYY-MM-DD)Result ValueUnit of MeasureExceedance
Antimony2025-04-07<0.06μ g/LNo
Arsenic2025-04-07<0.2μ g/LNo
Barium2025-04-0737.8μ g/LNo
Boron2025-04-0711μ g/LNo
Cadmium2025-04-07<0.03μ g/LNo
Chromium2025-04-070.25μ g/LNo
Mercury2025-04-07<0.01μ g/LNo
Selenium2025-04-070.05μ g/LNo
Uranium2025-04-070.004μ g/LNo
1st Quarter Nitrite2025-02-03<0.05mg/LNo
2nd Quarter Nitrite2025-05-05<0.05mg/LNo
3rd Quarter Nitrite2025-08-05<0.05mg/LNo
4th Quarter Nitrite2025-11-03<0.05mg/LNo
1st Quarter Nitrate2025-02-030.18mg/LNo
2nd Quarter Nitrate2025-05-050.09mg/LNo
3rd Quarter Nitrate2025-08-050.08mg/LNo
4th Quarter Nitrate2025-11-030.05mg/LNo
Sodium2025-04-0715.0mg/LNo

Smiths Falls Drinking Water System <u><strong>2025 Annual Report</strong></u>

ParameterSample Date (YYYY-MM-DD)Result Value (ug/L)Rolling Annual Average Quarter (ug/L)Exceedance
HAA5 1st Quarter2025-02-0325.446.8No
HAA5 2nd Quarter2025-05-0546.243.3No
HAA5 3rd Quarter2025-08-0541.440.3No
HAA5 4th Quarter2025-11-0327.935.2No

Notes:

  1. Maximum Allowable Concentration (MAC) for HAA is based on a four-quarter rolling annual average of 0.080 mg/L or 80.0 ug/L

  2. Granular activated carbon (GAC) changed out in all three filters beginning of April

Summary of lead testing under Schedule 15.1 during this reporting period & MDWL #164-<u><strong>101 Issue #6</strong></u> Schedule C, Section 6.6 Range of Lead Results Number of Range of Lead Results Number of

Location TypeNumber of Total SamplesRange of Lead Results 1st One Litre Sample min# - max # (mg/L)Number of Exceedances 1st SampleRange of Lead Results 2nd One Litre Sample min# - max # (mg/L)Number of Exceedances 2nd Sample
Plumbing - residential220.000130 - 0.002410050.000100 - 0.0198007
Plumbing - non residential0N/AN/AN/AN/A
Distribution40.000030 - 0.0001700N/AN/A
Finished Water30.000020 - 0.0000200N/AN/A
Location TypeNumber of Total samplespH (min # - max #)Number of Total samplesTemperature °C (min # - max #)
Plumbing - residential227.23 - 7.92228.4 - 21.5
Plumbing - non residential0N/A0N/A
Distribution47.54 - 7.7949.8 - 21.2
Finished Water37.22 - 7.67312.0 - 23.7
Location TypeNumber of Total samplesAlkalinity mg/L (min # - max #)
Plumbing - residential2279 - 114
Plumbing - non-residential0N/A
Distribution484 - 89
Finished Water379 - 87

Notes:

  1. Maximum Allowable Concentration (MAC) for lead is 0.010 mg/L or 10.0 ug/L.

  2. Finished water and Distribution lead samples above 0.010 mg/L or 10.0 ug/L are reportable to SAC and Health Unit.

  3. Plumbing samples from residential or non-residential, the occupant receives a letter to indicate if a sample is above the MAC, the results and an information sheet on lead.


Summary of Organic parameters sampled during this reporting period or the <u><strong>most recent sample results</strong></u> Parameter Sample Date Result Unit of Exceedance

ParameterSample Date (YYYY-MM-DD)Result ValueUnit of MeasureExceedance
Alachlor2025-04-07<0.02μ g/LNo
Atrazine2025-04-07<0.01μ g/LNo
Atrazine + N-dealkylated metabolites2025-04-07<0.01μ g/LNo
Azinphos-methyl2025-04-072μ g/LNo
Benzene2025-04-070.32μ g/LNo
Benzo(a)pyrene2025-04-070.004μ g/LNo
Bromoxynil2025-04-070.33μ g/LNo
Carbaryl2025-04-07<0.05μ g/LNo
Carbofuran2025-04-07<0.01μ g/LNo
Carbon Tetrachloride2025-04-07<0.17μ g/LNo
Chlorpyrifos2025-04-07<0.02μ g/LNo
Desethyl atrazine2025-04-07<0.01μ g/LNo
Diazinon2025-04-07<0.02μ g/LNo
Dicamba2025-04-07<0.20μ g/LNo
1,2-Dichlorobenzene2025-04-07<0.41μ g/LNo
1,4-Dichlorobenzene2025-04-07<0.36μ g/LNo
1,1-Dichloroethylene (vinylidene chloride)2025-04-07<0.33μ g/LNo
1,2-Dichloroethane2025-04-07<0.35μ g/LNo
Dichloromethane2025-04-07<0.35μ g/LNo
2,4-Dichlorophenol2025-04-07<0.15μ g/LNo
2,4-Dichlorophenoxy acetic acid (2,4-D)2025-04-07<0.19μ g/LNo
Diclofop-methyl2025-04-07<0.40μ g/LNo
Dimethoate2025-04-07<0.06μ g/LNo
Diquat2025-04-07<1μ g/LNo
Diuron2025-04-07<0.03μ g/LNo
Glyphosate2025-04-07<1μ g/LNo
Malathion2025-04-07<0.02μ g/LNo
2-Methyl-4-chlorophenoxyacetic acid (MCPA)2025-04-07<0.00012μ g/LNo
Metolachlor2025-04-07<0.01μ g/LNo
Metribuzin2025-04-07<0.02μ g/LNo
Monochlorobenzene2025-04-07<0.03μ g/LNo
Paraquat2025-04-07<1μ g/LNo
Pentachlorophenol2025-04-07<0.15μ g/LNo
Phorate2025-04-07<0.01μ g/LNo
Picloram2025-04-07<1μ g/LNo
Polychlorinated Biphenyls (PCB)2025-04-07<0.04μ g/LNo
Prometryne2025-04-07<0.03μ g/LNo
Simazine2025-04-07<0.01μ g/LNo
Terbufos2025-04-07<0.01μ g/LNo
Tetrachloroethylene (perchloroethylene)2025-04-07<0.35μ g/LNo
2,3,4,6-Tetrachlorophenol2025-04-07<0.20μ g/LNo
Triallate2025-04-07<0.01μ g/LNo
Trichloroethylene2025-04-07<0.44μ g/LNo
2,4,6-Trichlorophenol2025-04-07<0.25μ g/LNo
Trifluralin2025-04-07<0.02μ g/LNo
Vinyl Chloride2025-04-07<0.17μ g/LNo

Smiths Falls Drinking Water System <u><strong>2025 Annual Report</strong></u>

List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed in Schedule 2 of Ontario Drinking Water Quality Standards. Parameter Result Value Unit of Measure Date of Sample

ParameterResult ValueUnit of MeasureDate of Sample

Glossary

AWQI = adverse water quality indicator

CFU = colony forming units

DWS = drinking water system

DS = distribution system

EA = Environmental Assessment

HAA5 = total haloacetic acid

mg/L = milligrams per liter

MDWL = Municipal Drinking Water License

TTHM = trihalomethane

ug/L = micrograms per liter

WTP = water treatment plant

Contact for more information:

Sarah E. Cooke

Water & Wastewater Compliance Coordinator

Phone: 613-283-4124 ext. 5502

Email: <u>scooke@smithsfalls.ca</u>

Andrew MacNaughton

Manager Water/Wastewater Treatment

Phone: 613-283-4124 ext. 5501

Email: <u>amacnaughton@smithsfalls.ca</u>