<u>TEMPORARY EVENT TENTS AND THE ONTARIO BUILDING CODE (OBC)</u>
Tents less than 6_0 m² in area
-
No building permit is required. Tents between 61m² and 225 m² in area (646 sq.ft.-2420 sq.ft.)
-
Building permit is required with Professional Engineer Tent Assembly/ Anchorage specs.
-
Application must include a completed Provincial application form (available on the website under the Building Division page), <u>site plan</u> indicating the location of the tent with setbacks to other buildings and property lines shown.
-
Must maintain 3m to property lines and other structures.
-
Ground enclosed by the tent must be clear of flammable material (grass cut short is acceptable)
-
<u>Copy of flame resistance certification required</u>- must state compliance with either NFPA 701 or CAN/UC-S109
-
Access must be provided for firefighting (must be easily approachable by emergency personnel).
Tents <u>greater than 225m² in area</u> (over 2420 sq.ft.)
- All requirements for tents 61m²- 225m² apply as well as the following:
- <u>Professional Engineer</u> must design the supporting framing structure and anchorage system, sign a commitment to review form and inspect the tent after it is erected, but before it is in use.
- <u>A copy of the Engineer's report is to be submitted to the Building Division</u>
- Sanitary facilities must be provided in compliance with the Building Code.
General Requirements
- If more than one tent is used and they/lre placed within 3m of each other, the total area of all such tents are considered as if they were only one tent
- Building permit application must be submitted at least 10 days prior to erection
- The addition of bleachers or side walls automatically puts the tent into the greater than 225m² category regardless of size An inspection is required prior to the tent being put into use. Fire prevention staff accompany the Building Inspector to perform a joint inspection organized via the Building Division.