TOWN OF SMITHS FALLS
S
SMITHS FALLS RISE AT THE FALLS
SMITHS FALLS DRINKING WATER SYSTEM 2023 ANNUAL REPORT R1
Smiths Falls Drinking Water System <u><strong>2023 Annual Report R1</strong></u>
Drinking-Water System Number:
Drinking-Water System Name:
Drinking-Water System Owner:
Drinking-Water System Category:
Period being reported:
| 220001307 |
|---|
| Smiths Falls Drinking Water System |
| Corporation of the Town of Smiths Falls |
| Large Municipal Drinking Water System |
| January 1st to December 31st, 2023 |
| Complete if your Category is LargeMunicipal Residential or Small MunicipalResidentialDoes your Drinking-Water System serve more than 10,000 people?Yes [ ] No [✓]Is your annual report available to the public at no charge on a web site on the Internet?Yes [✓] No [ ]Location where Annual Report required under O. Reg. 170/03 Schedule 11 will be available to the public.www.smithsfalls.caSmiths Falls Town Hall Complex77 Beckwith St. NSmiths Falls, ON K7A 4T6 | Complete for all other Categories.Number of Designated Facilities served: N/ADid you provide a copy of your annual report to all Designated Facilities you serve? N/aNumber of Interested Authorities you report to: N/ADid you provide a copy of your annual report to all Interested Authorities you report to for each Designated Facility? N/A |
|---|
List all Drinking-Water Systems (if any), which receive all of their drinking water from your system:
| Drinking Water System Name | Drinking Water System Number |
|---|---|
| Atironto Subdivision – Montague Township | 260006828 |
Did you provide a copy of your annual report to all Drinking-Water System owners that are connected to you and to whom you provide all of its drinking water?
Yes [✓] No [ ]
Indicate how you notified system users that your annual report is available, and is free of charge.
[✓] Public access/notice via the web
[ ] Public access/notice via a newspaper
Describe your Drinking-Water System
The Smiths Falls Drinking Water System is comprised of the Water Treatment Plant (WTP) and Distribution system (WDS) which together provides a supply of potable water to the residents and businesses of the Town of Smiths Falls.
The WTP is a Class IV high-rate dissolved air floatation (AquaDAF ®) surface water plant having an approved design capacity of 14,000 m<sup>3</sup>/d with a future expansion to 18,000 m<sup>3</sup>/d. Raw water for the treatment process is drawn from the Rideau River (surface water). The intake structure is located upstream of the WTP approximately 170m. The intake consists of a concrete structure and a 762-millimeter diameter concrete pipe connecting the intake to the diversion chamber where the raw water is directed into the WTP.
Low lift pumps supply water to the AquaDAF ® which is a high-rate dissolved air floatation clarifier. A coagulant & polymer are mixed with the Raw Water to aid in particle removal. Dissolved air will float these particles to form a blanket of sludge which is discharged to the wastewater collection system.
Clarified water flows to 3 granular activate carbon (GAC) & sand filters where further particle removal will take place.
Processes involved include: UV disinfection; chlorination with chlorine gas; corrosion control; fluoridation; residue management and de-chlorination.
The WDS is a Class I subsystem, consisting of 61.94 kilometers (km) of mains, 1096 valves, 332 hydrants and 3010 house services. With a 49.2 meter (m) high water tower that contains 945.75 cubic meters (m<sup>3</sup>) of storage.
List all water treatment chemicals used over this reporting period
| CHEMICAL NAME | USE | SUPPLIER |
|---|---|---|
| PAX-XL6 | Coagulant | Kemira |
| Magnafloc LT22s | Polymer | Northland Chemical |
| Chlorine Gas | Disinfection | Brenntag |
| Sodium Hydroxide | Corrosion Control | Brenntag |
| Fluorosilicic Acid | Fluoride | PVS Benson |
| Calcium Thiosulfate | De-chlorination | Cleartech |
| Sodium Chlorite | Pre-treatment Zebra Mussel | PVS Benson |
Were any significant expenses incurred to?
[✓] Install required equipment
[✓] Repair required equipment
[ ] Replace required equipment
Please provide a brief description and a breakdown of monetary expenses incurred
S GAC Replacement – $385,507
S High lift pump rebuild - $13,006
S Low lift pump rebuild - $7,017
S New Tower detailed design/Site clearing - $152,700
S WD Valve Maintenance trailer - $126,651
S Catherine Street reconstruction - $1,145,399
S Zebre Mussell/THMM reduction - $96,060
S AquaDAF 1&2 Actuators - $20,723
S Water meters - $59,315
S Old Water Tower Communications - $11,521
S Water Plant Exterior doors - $58,308
Provide details on the notices submitted in accordance with subsection 18(1) of the Safe Drinking Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to Spills Action Centre
| Incident Date | Parameter | Result | Unit of Measure | Corrective Action | Corrective Action Date |
|---|---|---|---|---|---|
| AWQI 161776 (2023-Apr-18) | Total Coliform (TC) | 1 | 1 colony forming unit (CFU)/100mL | TC present at the Union St flusher. Re-samples collected 2023-Apr-18 from Union St flusher, FAC was 0.60mg/L, downstream sample collected at hydrant (Book Binding) FAC was 1.53 mg/L, no upstream sample. Verbal received on 2023-Apr-20 that samples zero for TC and E. Coli | 2023-Apr-18 Section 2B submitted 2023-Apr-24 |
| Incident #1-3JETDQ (2023-Jun-13) | Tower overflow | N/A | N/A | Tower briefly overflowed due to issues with instrumentation and SCADA. Issue resolved by looking into program | 2023-Jun-13 |
| Incident #1-3MTBF5 (2023-Jul-13) | Tower overflow | N/A | N/A | Tower briefly overflowed due to issues with instrumentation and SCADA. Issue resolved by looking into program | 2023-Jul-13 |
Microbiological testing completed under Schedule 10, 11 or 12 of Regulation 170/03 during this reporting period.
| Number of Samples | Range of E. coli Results (min #) - (max #) (CFU/100mL) | Range of Total Coliform Results (min #) - (max #) (CFU/100mL) | Number of HPC Samples | Range of HPC Results (min #) - (max #) (CFU/100mL) | |
|---|---|---|---|---|---|
| Raw | 53 | 0 - 101 | 10 - 500 | N/A | N/A |
| Treated | 52 | 0 - 0 | 0 - 0 | 52 | 10 - 300 |
| Distribution - Routine | 311 | 0 - 0 | 0 - 1* | 311 | <10 - 150 |
| Distribution Water main Repairs/new installations/service repairs | 61 | 0 - 0 | 0 - 1** | 58 | <10 - 300 |
*AWQI 161776 see above table for more information
Smiths Falls Drinking Water System 2023 Annual Report R1
** Non-regulatory sample Catherine St. capital project
Operational testing completed under Schedule 7, 8 or 9 of Regulation 170/03 during the period covered by this Annual Report.
| Parameter Tested - (Online Analyzers) | Number of Grab Samples | Range of Results Minimum | Range of Results Average | Range of Results Maximum |
|---|---|---|---|---|
| Turbidity - Raw Water (NTU) AIT 102 | Continuous Monitoring1 | 0.000 | 0.806 | 49.992 |
| Turbidity - Raw Water (NTU) | (365 bench test) | 0.297 | 0.103 | 3.86 |
| Turbidity - Filter #1 (NTU) AIT 111 | Continuous Monitoring2 | 0.000 | 0.033 | 5.00 |
| Turbidity - Filter #1 (NTU) | (51 bench test) | 0.047 | 0.103 | 0.178 |
| Turbidity - Filter #2 (NTU) AIT 121 | Continuous Monitoring2 | 0.000 | 0.035 | 5.00 |
| Turbidity - Filter #2 (NTU) | (52 bench test) | 0.045 | 0.113 | 0.217 |
| Turbidity - Filter #3 (NTU) AIT 131 | Continuous Monitoring2 | 0.000 | 0.033 | 5.00 |
| Turbidity - Filter #3 (NTU) | (51 bench test) | 0.033 | 0.128 | 0.365 |
| Turbidity - Finished Water (NTU) AIT 184 | Continuous Monitoring3 | 0.000 | 0.046 | 5.000 |
| Turbidity - Finished Water (NTU) | (248 bench test) | 0.030 | 0.091 | 0.363 |
| Chlorine Total - Zebra Mussel (operation May to October mg/L) AIT 103 | Continuous Monitoring7 Total Chlorine | N/A | N/A | N/A |
| Chlorine Total - Zebra Mussel (operation May to October mg/L) | (0 bench test)8 | N/A | N/A | N/A |
| Chlorine Free - Pre-Reservoir (mg/L) AIT 165 | Continuous Monitoring5 Free Chlorine | 0.00 | 2.29 | 5.00 |
| Chlorine Free - Pre-Reservoir (mg/L) | (52 bench test) | 1.24 | 2.04 | 2.74 |
| Chlorine Free - Post Reservoir (mg/L) AIT 180 | Continuous Monitoring5 Free Chlorine | 0.00 | 1.78 | 3.02 |
| Chlorine Free - Post Reservoir (mg/L) | (52 bench test) | 1.07 | 1.61 | 2.23 |
| Chlorine Free - Finished Water (mg/L) AIT 185 | Continuous Monitoring5 Free Chlorine | 0.00 | 1.75 | 2.35 |
| Chlorine Free - Finished Water (mg/L) | (249 bench test) | 1.12 | 1.68 | 2.13 |
| Chlorine Total - Finished Water (mg/L) AIT 186 | Continuous Monitoring6 Total Chlorine | 0.00 | 1.99 | 2.63 |
| Chlorine Total - Finished Water (mg/L) | (249 bench test) | 1.40 | 1.90 | 2.49 |
| Fluoride - Finished Water (mg/L) AIT 187 | Continuous Monitoring4 | 0.00 | 0.62 | 2.00 |
| Fluoride - Finished Water (mg/L) | (365 bench test) | 0.24 | 0.57 | 1.15 |
| UV Transmittance (%) AIT 160 | Continuous Monitoring9 | 70.0 | 96.6 | 100.0 |
| UV Transmittance (%) | (246 bench test) | 80.8 | 92.8 | 101.4 |
<u><strong>Notes for above table operational testing completed under Schedule 7, 8 or 9:</strong></u>
-
High raw water turbidity spikes occur when the low lift pumps (LLP) start and stop, maintenance, calibration and flushing of lines.
-
High filter turbidity results of filter backwash, process upset or calibration.
-
High finished water turbidity results of high lift pumps (HLP) starting or calibration.
-
High fluoride readings occur on HLP starts, maintenance or calibration while chemical system was off.
Smiths Falls Drinking Water System <u>2023 Annual Report R1</u>
-
Low free chlorine residual (pre-reservoir, post reservoir and finished water) result of generator backup power testing, maintenance, or calibration.
-
Low total chlorine residual (finished water) result of generator backup power testing, maintenance, or calibration.
-
High total chlorine residuals (for zebra mussel control) can be due the sampling alternates between intake and LLP header.
-
Bench tests for total chlorine (zebra mussel) are sampled from the raw water stainless steel sample tap located in pump gallery or raw water sample tap in lab.
-
Low UV transmittance result of generator backup power testing, maintenance, calibration or Optiview failure.
Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument. Date of legal Parameter Date Sampled Result Quarterly Rolling
| Date of legal instrument issued | Parameter | Date Sampled (YYYY-MM-DD) | Result (μ g/L) | Quarterly Average (μ g/L) | Rolling Annual Average Quarter (μ g/L) |
|---|---|---|---|---|---|
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-Jan-03 | 58.0 | 51.7 | 74.0 |
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-Feb-06 | 47.0 | 51.7 | 74.0 |
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-Mar-06 | 50.0 | 51.7 | 74.0 |
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-Apr-03 | 63.0 | 32.0 | 63.2 |
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-May-01 | 7.0 | 32.0 | 63.2 |
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-Jun-05 | 26.0 | 32.0 | 63.2 |
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-Jul-04 | 41.0 | 53.3 | 51.4 |
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-Aug-08 | 45.0 | 53.3 | 51.4 |
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-Sept-05 | 74.0 | 53.3 | 51.4 |
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-Oct-02 | 52.0 | 41.0 | 44.5 |
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-Nov-06 | 32.0 | 41.0 | 44.5 |
| Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06 | TTHM | 2023-Dec-04 | 39.0 | 41.0 | 44.5 |
<u><strong>Notes:</strong></u>
-
Maximum Allowable Concentration (MAC) for THM is based on a four-quarter rolling annual average of 0.100 mg/L or 100.0 ug/L
-
Granular activated carbon (GAC) changed out in all three filters beginning of April
Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument.
| Date of legal instrument issued | Parameter | Date Sampled (YYYY-MM-DD) | Result -Monthly TSS Average (mg/L) | Result -Monthly Grab Average Total Chlorine (mg/L) |
|---|---|---|---|---|
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-Jan-10 | 9.30 | 0.01 |
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-Feb-14 | 3.40 | 0.02 |
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-Mar-09 | 8.07 | 0.00 |
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-Apr-21 | 3.93 | 0.02 |
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-May-15 | 6.07 | 0.01 |
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-Jun-08 | 3.47 | 0.01 |
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-Jul-10 | 1.73 | 0.01 |
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-Aug-14 | 7.23 | 0.02 |
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-Sept-15 | 2.17 | 0.02 |
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-Oct-13 | 4.87 | 0.02 |
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-Nov-10 | 4.60 | 0.01 |
| Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3) | TSS (grab sample) | 2023-Dec-20 | 4.20 | 0.04 |
| Annual average | 4.92 | 0.02 |
Summary of Inorganic parameters tested during this reporting period or the most recent sample results
Smiths Falls Drinking Water System <u><strong>2023 Annual Report R1</strong></u>
| Parameter | Sample Date (YYYY-MM-DD) | Result Value | Unit of Measure | Exceedance |
|---|---|---|---|---|
| Antimony | 2023-Apr-03 | <0.6 | μ g/L | No |
| Arsenic | 2023-Apr-03 | <0.2 | μ g/L | No |
| Barium | 2023-Apr-03 | 38.4 | μ g/L | No |
| Boron | 2023-Apr-03 | 12 | μ g/L | No |
| Cadmium | 2023-Apr-03 | 0.003 | μ g/L | No |
| Chromium | 2023-Apr-03 | 0.31 | μ g/L | No |
| Mercury | 2023-Apr-03 | <0.01 | μ g/L | No |
| Selenium | 2023-Apr-03 | 0.05 | μ g/L | No |
| Uranium | 2023-Apr-03 | 0.021 | μ g/L | No |
| 1st Quarter Nitrite | 2023-Feb-06 | <0.05 | mg/L | No |
| 2nd Quarter Nitrite | 2023-May-01 | <0.05 | mg/L | No |
| 3rd Quarter Nitrite | 2023-Aug-08 | <0.05 | mg/L | No |
| 4th Quarter Nitrite | 2023-Nov-06 | 0.05 | mg/L | No |
| 1st Quarter Nitrate | 2023-Feb-06 | 0.18 | mg/L | No |
| 2nd Quarter Nitrate | 2023-May-01 | <0.05 | mg/L | No |
| 3rd Quarter Nitrate | 2023-Aug-08 | <0.05 | mg/L | No |
| 4th Quarter Nitrate | 2023-Nov-06 | 0.05 | mg/L | No |
| Sodium | 2023-Apr-03 | 13.8 | mg/L | No |
| Parameter | Sample Date (YYYY-MM-DD) | Result Value (ug/L) | Rolling Annual Average Quarter (ug/L) | Exceedance |
|---|---|---|---|---|
| HAA5 1st Quarter | 2023-Feb-06 | 32.1 | 49.4 | No |
| HAA5 2nd Quarter | 2023-May-01 | 5.3 | 35.9 | No |
| HAA5 3rd Quarter | 2023-Aug-08 | 36.9 | 31.1 | No |
| HAA5 4th Quarter | 2023-Nov-06 | 30.7 | 26.3 | No |
Notes:
-
Maximum Allowable Concentration (MAC) for HAA is based on a four-quarter rolling annual average of 0.080 mg/L or 80.0 ug/L
-
Granular activated carbon (GAC) changed out in all three filters beginning of April
Summary of lead testing under Schedule 15.1 during this reporting period & MDWL #164-<u><strong>101 Issue #6</strong></u> Schedule C, Section 6.6 Range of Lead Results Number of Range of Lead Results Number of
| Location Type | Number of Total Samples | Range of Lead Results 1st One Litre Sample min# – max # (mg/L) | Number of Exceedances 1st Sample | Range of Lead Results 2nd One Litre Sample min# – max # (mg/L) | Number of Exceedances 2nd Sample |
|---|---|---|---|---|---|
| Plumbing – residential | 23 | 0.000080 – 0.059700 | 6 | 0.000050 – 0.063000 | 6 |
| Plumbing – non residential | 0 | N/A | N/A | N/A | N/A |
| Distribution | 4 | 0.000030 – 0.000960 | 0 | N/A | N/A |
| Finished Water | 4 | 0.000020 – 0.000020 | 0 | N/A | N/A |
| Location Type | Number of Total samples | pH (min # - max #) | Number of Total samples | Temperature °C (min # - max #) |
|---|---|---|---|---|
| Plumbing - residential | 23 | 7.12 - 7.83 | 23 | 6.7 - 22.1 |
| Plumbing - non residential | 0 | N/A | N/A | N/A |
| Distribution | 4 | 7.53 - 7.80 | 4 | 4.8 - 21.6 |
| Finished Water | 4 | 7.40 - 7.70 | 4 | 7.5 - 22.9 |
| Location Type | Number of Total samples | Alkalinity mg/L (min # - max #) |
|---|---|---|
| Plumbing - residential | 23 | 72 - 105 |
| Plumbing - non-residential | 0 | N/A |
| Distribution | 4 | 73 - 78 |
| Finished Water | 4 | 77 - 97 |
Notes:
-
Maximum Allowable Concentration (MAC) for lead is 0.010 mg/L or 10.0 ug/L.
-
Only Distribution lead samples above 0.010 mg/L or 10.0 ug/L are reportable.
-
Plumbing samples from residential or non-residential, the occupant receives a letter to indicate if a sample is above the MAC, the results and an information sheet on lead.
Summary of Organic parameters sampled during this reporting period or the <u><strong>most recent sample results</strong></u> Parameter Sample Date Result Unit of Exceedance
| Parameter | Sample Date (YYYY-MM-DD) | Result Value | Unit of Measure | Exceedance |
|---|---|---|---|---|
| Alachlor | 2023-Apr-03 | <0.02 | μ g/L | No |
| Atrazine | 2023-Apr-03 | <0.01 | μ g/L | No |
| Atrazine + N-dealkylated metabolites | 2023-Apr-03 | <0.01 | μ g/L | No |
| Azinphos-methyl | 2023-Apr-03 | <0.05 | μ g/L | No |
| Benzene | 2023-Apr-03 | <0.32 | μ g/L | No |
| Benzo(a)pyrene | 2023-Apr-03 | <0.004 | μ g/L | No |
| Bromoxynil | 2023-Apr-03 | <0.33 | μ g/L | No |
| Carbaryl | 2023-Apr-03 | <0.05 | μ g/L | No |
| Carbofuran | 2023-Apr-03 | <0.01 | μ g/L | No |
| Carbon Tetrachloride | 2023-Apr-03 | <0.17 | μ g/L | No |
| Chlorpyrifos | 2023-Apr-03 | <0.02 | μ g/L | No |
| Desethyl atrazine | 2023-Apr-03 | <0.01 | μ g/L | No |
| Diazinon | 2023-Apr-03 | <0.02 | μ g/L | No |
| Dicamba | 2023-Apr-03 | <0.20 | μ g/L | No |
| 1,2-Dichlorobenzene | 2023-Apr-03 | <0.41 | μ g/L | No |
| 1,4-Dichlorobenzene | 2023-Apr-03 | <0.36 | μ g/L | No |
| 1,1-Dichloroethylene (vinylidene chloride) | 2023-Apr-03 | <0.33 | μ g/L | No |
| 1,2-Dichloroethane | 2023-Apr-03 | <0.35 | μ g/L | No |
| Dichloromethane | 2023-Apr-03 | <0.35 | μ g/L | No |
| 2,4-Dichlorophenol | 2023-Apr-03 | <0.15 | μ g/L | No |
| 2,4-Dichlorophenoxy acetic acid (2,4-D) | 2023-Apr-03 | <0.19 | μ g/L | No |
| Diclofop-methyl | 2023-Apr-03 | <0.40 | μ g/L | No |
| Dimethoate | 2023-Apr-03 | <0.06 | μ g/L | No |
Smiths Falls Drinking Water System <u><strong>2023 Annual Report R1</strong></u>
| Diquat | 2023-Apr-03 | <1 | μ g/L | No |
|---|---|---|---|---|
| Diuron | 2023-Apr-03 | <0.03 | μ g/L | No |
| Glyphosate | 2023-Apr-03 | <1 | μ g/L | No |
| Malathion | 2023-Apr-03 | <0.02 | μ g/L | No |
| 2-Methyl-4-chlorophenoxyacetic acid (MCPA) | 2023-Apr-03 | <0.00012 | μ g/L | No |
| Metolachlor | 2023-Apr-03 | <0.01 | μ g/L | No |
| Metribuzin | 2023-Apr-03 | <0.02 | μ g/L | No |
| Monochlorobenzene | 2023-Apr-03 | <0.3 | μ g/L | No |
| Paraquat | 2023-Apr-03 | <1 | μ g/L | No |
| Pentachlorophenol | 2023-Apr-03 | <0.15 | μ g/L | No |
| Phorate | 2023-Apr-03 | <0.01 | μ g/L | No |
| Picloram | 2023-Apr-03 | <1 | μ g/L | No |
| Polychlorinated Biphenyls (PCB) | 2023-Apr-03 | <0.04 | μ g/L | No |
| Prometryne | 2023-Apr-03 | <0.03 | μ g/L | No |
| Simazine | 2023-Apr-03 | <0.01 | μ g/L | No |
| Terbufos | 2023-Apr-03 | <0.01 | μ g/L | No |
| Tetrachloroethylene (perchloroethylene) | 2023-Apr-03 | <0.35 | μ g/L | No |
| 2,3,4,6-Tetrachlorophenol | 2023-Apr-03 | <0.20 | μ g/L | No |
| Triallate | 2023-Apr-03 | <0.01 | μ g/L | No |
| Trichloroethylene | 2023-Apr-03 | <0.44 | μ g/L | No |
| 2,4,6-Trichlorophenol | 2023-Apr-03 | <0.25 | μ g/L | No |
| Trifluralin | 2023-Apr-03 | <0.02 | μ g/L | No |
| Vinyl Chloride | 2023-Apr-03 | <0.17 | μ g/L | No |
List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed in Schedule 2 of Ontario Drinking Water Quality Standards. Parameter Result Value Unit of Measure Date of Sample
| Parameter | Result Value | Unit of Measure | Date of Sample |
|---|---|---|---|
Glossary
AWQI = adverse water quality indicator
CFU = colony forming units
DWS = drinking water system
DS = distribution system
EA = Environmental Assessment
HAA5 = total haloacetic acid
mg/L = milligrams per liter
MDWL = Municipal Drinking Water License
TTHM = trihalomethane
ug/L = micrograms per liter
WTP = water treatment plant
Contact for more information:
Sarah E. Cooke
Water & Wastewater Compliance Coordinator
Phone: 613-283-4124 ext. 5502
Email: <u>scooke@smithsfalls.ca</u>
Smiths Falls Drinking Water System <u>2023 Annual Report R1</u>
Jason Barlow Manager Water & Wastewater Phone: 613-283-4124 ext. 5501 Email: <u>jbarlow@smithsfalls.ca</u>
O. Reg. 170/03 - Section 11 Annual Reports Page 10 of 10 Revised March 18, 2024 R1