Back to the archive
Public document · Water

2023 Drinking Water System Annual Report R1

Public source material preserved in the Field Guide. Consult the original for authoritative wording and current status.

Source text

TOWN OF SMITHS FALLS

S

SMITHS FALLS RISE AT THE FALLS

SMITHS FALLS DRINKING WATER SYSTEM 2023 ANNUAL REPORT R1


Smiths Falls Drinking Water System <u><strong>2023 Annual Report R1</strong></u>

Drinking-Water System Number:
Drinking-Water System Name: Drinking-Water System Owner: Drinking-Water System Category: Period being reported:

220001307
Smiths Falls Drinking Water System
Corporation of the Town of Smiths Falls
Large Municipal Drinking Water System
January 1st to December 31st, 2023
Complete if your Category is LargeMunicipal Residential or Small MunicipalResidentialDoes your Drinking-Water System serve more than 10,000 people?Yes [ ] No [✓]Is your annual report available to the public at no charge on a web site on the Internet?Yes [✓] No [ ]Location where Annual Report required under O. Reg. 170/03 Schedule 11 will be available to the public.www.smithsfalls.caSmiths Falls Town Hall Complex77 Beckwith St. NSmiths Falls, ON K7A 4T6Complete for all other Categories.Number of Designated Facilities served: N/ADid you provide a copy of your annual report to all Designated Facilities you serve? N/aNumber of Interested Authorities you report to: N/ADid you provide a copy of your annual report to all Interested Authorities you report to for each Designated Facility? N/A

List all Drinking-Water Systems (if any), which receive all of their drinking water from your system:

Drinking Water System NameDrinking Water System Number
Atironto Subdivision – Montague Township260006828

Did you provide a copy of your annual report to all Drinking-Water System owners that are connected to you and to whom you provide all of its drinking water?

Yes [✓] No [ ]

Indicate how you notified system users that your annual report is available, and is free of charge.

[✓] Public access/notice via the web
[ ] Public access/notice via a newspaper


Describe your Drinking-Water System

The Smiths Falls Drinking Water System is comprised of the Water Treatment Plant (WTP) and Distribution system (WDS) which together provides a supply of potable water to the residents and businesses of the Town of Smiths Falls.

The WTP is a Class IV high-rate dissolved air floatation (AquaDAF ®) surface water plant having an approved design capacity of 14,000 m<sup>3</sup>/d with a future expansion to 18,000 m<sup>3</sup>/d. Raw water for the treatment process is drawn from the Rideau River (surface water). The intake structure is located upstream of the WTP approximately 170m. The intake consists of a concrete structure and a 762-millimeter diameter concrete pipe connecting the intake to the diversion chamber where the raw water is directed into the WTP.

Low lift pumps supply water to the AquaDAF ® which is a high-rate dissolved air floatation clarifier. A coagulant & polymer are mixed with the Raw Water to aid in particle removal. Dissolved air will float these particles to form a blanket of sludge which is discharged to the wastewater collection system.

Clarified water flows to 3 granular activate carbon (GAC) & sand filters where further particle removal will take place.

Processes involved include: UV disinfection; chlorination with chlorine gas; corrosion control; fluoridation; residue management and de-chlorination.

The WDS is a Class I subsystem, consisting of 61.94 kilometers (km) of mains, 1096 valves, 332 hydrants and 3010 house services. With a 49.2 meter (m) high water tower that contains 945.75 cubic meters (m<sup>3</sup>) of storage.

List all water treatment chemicals used over this reporting period

CHEMICAL NAMEUSESUPPLIER
PAX-XL6CoagulantKemira
Magnafloc LT22sPolymerNorthland Chemical
Chlorine GasDisinfectionBrenntag
Sodium HydroxideCorrosion ControlBrenntag
Fluorosilicic AcidFluoridePVS Benson
Calcium ThiosulfateDe-chlorinationCleartech
Sodium ChloritePre-treatment Zebra MusselPVS Benson

Were any significant expenses incurred to?

[✓] Install required equipment

[✓] Repair required equipment

[ ] Replace required equipment


Please provide a brief description and a breakdown of monetary expenses incurred

S GAC Replacement – $385,507

S High lift pump rebuild - $13,006

S Low lift pump rebuild - $7,017

S New Tower detailed design/Site clearing - $152,700

S WD Valve Maintenance trailer - $126,651

S Catherine Street reconstruction - $1,145,399

S Zebre Mussell/THMM reduction - $96,060

S AquaDAF 1&2 Actuators - $20,723

S Water meters - $59,315

S Old Water Tower Communications - $11,521

S Water Plant Exterior doors - $58,308

Provide details on the notices submitted in accordance with subsection 18(1) of the Safe Drinking Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to Spills Action Centre

Incident DateParameterResultUnit of MeasureCorrective ActionCorrective Action Date
AWQI 161776 (2023-Apr-18)Total Coliform (TC)11 colony forming unit (CFU)/100mLTC present at the Union St flusher. Re-samples collected 2023-Apr-18 from Union St flusher, FAC was 0.60mg/L, downstream sample collected at hydrant (Book Binding) FAC was 1.53 mg/L, no upstream sample. Verbal received on 2023-Apr-20 that samples zero for TC and E. Coli2023-Apr-18 Section 2B submitted 2023-Apr-24
Incident #1-3JETDQ (2023-Jun-13)Tower overflowN/AN/ATower briefly overflowed due to issues with instrumentation and SCADA. Issue resolved by looking into program2023-Jun-13
Incident #1-3MTBF5 (2023-Jul-13)Tower overflowN/AN/ATower briefly overflowed due to issues with instrumentation and SCADA. Issue resolved by looking into program2023-Jul-13

Microbiological testing completed under Schedule 10, 11 or 12 of Regulation 170/03 during this reporting period.

Number of SamplesRange of E. coli Results (min #) - (max #) (CFU/100mL)Range of Total Coliform Results (min #) - (max #) (CFU/100mL)Number of HPC SamplesRange of HPC Results (min #) - (max #) (CFU/100mL)
Raw530 - 10110 - 500N/AN/A
Treated520 - 00 - 05210 - 300
Distribution - Routine3110 - 00 - 1*311<10 - 150
Distribution Water main Repairs/new installations/service repairs610 - 00 - 1**58<10 - 300

*AWQI 161776 see above table for more information


Smiths Falls Drinking Water System 2023 Annual Report R1

** Non-regulatory sample Catherine St. capital project

Operational testing completed under Schedule 7, 8 or 9 of Regulation 170/03 during the period covered by this Annual Report.

Parameter Tested - (Online Analyzers)Number of Grab SamplesRange of Results MinimumRange of Results AverageRange of Results Maximum
Turbidity - Raw Water (NTU) AIT 102Continuous Monitoring10.0000.80649.992
Turbidity - Raw Water (NTU)(365 bench test)0.2970.1033.86
Turbidity - Filter #1 (NTU) AIT 111Continuous Monitoring20.0000.0335.00
Turbidity - Filter #1 (NTU)(51 bench test)0.0470.1030.178
Turbidity - Filter #2 (NTU) AIT 121Continuous Monitoring20.0000.0355.00
Turbidity - Filter #2 (NTU)(52 bench test)0.0450.1130.217
Turbidity - Filter #3 (NTU) AIT 131Continuous Monitoring20.0000.0335.00
Turbidity - Filter #3 (NTU)(51 bench test)0.0330.1280.365
Turbidity - Finished Water (NTU) AIT 184Continuous Monitoring30.0000.0465.000
Turbidity - Finished Water (NTU)(248 bench test)0.0300.0910.363
Chlorine Total - Zebra Mussel (operation May to October mg/L) AIT 103Continuous Monitoring7 Total ChlorineN/AN/AN/A
Chlorine Total - Zebra Mussel (operation May to October mg/L)(0 bench test)8N/AN/AN/A
Chlorine Free - Pre-Reservoir (mg/L) AIT 165Continuous Monitoring5 Free Chlorine0.002.295.00
Chlorine Free - Pre-Reservoir (mg/L)(52 bench test)1.242.042.74
Chlorine Free - Post Reservoir (mg/L) AIT 180Continuous Monitoring5 Free Chlorine0.001.783.02
Chlorine Free - Post Reservoir (mg/L)(52 bench test)1.071.612.23
Chlorine Free - Finished Water (mg/L) AIT 185Continuous Monitoring5 Free Chlorine0.001.752.35
Chlorine Free - Finished Water (mg/L)(249 bench test)1.121.682.13
Chlorine Total - Finished Water (mg/L) AIT 186Continuous Monitoring6 Total Chlorine0.001.992.63
Chlorine Total - Finished Water (mg/L)(249 bench test)1.401.902.49
Fluoride - Finished Water (mg/L) AIT 187Continuous Monitoring40.000.622.00
Fluoride - Finished Water (mg/L)(365 bench test)0.240.571.15
UV Transmittance (%) AIT 160Continuous Monitoring970.096.6100.0
UV Transmittance (%)(246 bench test)80.892.8101.4

<u><strong>Notes for above table operational testing completed under Schedule 7, 8 or 9:</strong></u>

  1. High raw water turbidity spikes occur when the low lift pumps (LLP) start and stop, maintenance, calibration and flushing of lines.

  2. High filter turbidity results of filter backwash, process upset or calibration.

  3. High finished water turbidity results of high lift pumps (HLP) starting or calibration.

  4. High fluoride readings occur on HLP starts, maintenance or calibration while chemical system was off.


Smiths Falls Drinking Water System <u>2023 Annual Report R1</u>

  1. Low free chlorine residual (pre-reservoir, post reservoir and finished water) result of generator backup power testing, maintenance, or calibration.

  2. Low total chlorine residual (finished water) result of generator backup power testing, maintenance, or calibration.

  3. High total chlorine residuals (for zebra mussel control) can be due the sampling alternates between intake and LLP header.

  4. Bench tests for total chlorine (zebra mussel) are sampled from the raw water stainless steel sample tap located in pump gallery or raw water sample tap in lab.

  5. Low UV transmittance result of generator backup power testing, maintenance, calibration or Optiview failure.

Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument. Date of legal Parameter Date Sampled Result Quarterly Rolling

Date of legal instrument issuedParameterDate Sampled (YYYY-MM-DD)Result (μ g/L)Quarterly Average (μ g/L)Rolling Annual Average Quarter (μ g/L)
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-Jan-0358.051.774.0
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-Feb-0647.051.774.0
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-Mar-0650.051.774.0
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-Apr-0363.032.063.2
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-May-017.032.063.2
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-Jun-0526.032.063.2
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-Jul-0441.053.351.4
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-Aug-0845.053.351.4
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-Sept-0574.053.351.4
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-Oct-0252.041.044.5
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-Nov-0632.041.044.5
Municipal Drinking Water License #164-101 Issue #6 2021-Jun-06TTHM2023-Dec-0439.041.044.5

<u><strong>Notes:</strong></u>

  1. Maximum Allowable Concentration (MAC) for THM is based on a four-quarter rolling annual average of 0.100 mg/L or 100.0 ug/L

  2. Granular activated carbon (GAC) changed out in all three filters beginning of April

Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument.

Date of legal instrument issuedParameterDate Sampled (YYYY-MM-DD)Result -Monthly TSS Average (mg/L)Result -Monthly Grab Average Total Chlorine (mg/L)
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-Jan-109.300.01
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-Feb-143.400.02
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-Mar-098.070.00
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-Apr-213.930.02
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-May-156.070.01
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-Jun-083.470.01
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-Jul-101.730.01
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-Aug-147.230.02
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-Sept-152.170.02
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-Oct-134.870.02
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-Nov-104.600.01
Municipal Drinking Water License #164-101 issue #6 (Schedule C section 1.5 table 3)TSS (grab sample)2023-Dec-204.200.04
Annual average4.920.02

Summary of Inorganic parameters tested during this reporting period or the most recent sample results


Smiths Falls Drinking Water System <u><strong>2023 Annual Report R1</strong></u>

ParameterSample Date (YYYY-MM-DD)Result ValueUnit of MeasureExceedance
Antimony2023-Apr-03<0.6μ g/LNo
Arsenic2023-Apr-03<0.2μ g/LNo
Barium2023-Apr-0338.4μ g/LNo
Boron2023-Apr-0312μ g/LNo
Cadmium2023-Apr-030.003μ g/LNo
Chromium2023-Apr-030.31μ g/LNo
Mercury2023-Apr-03<0.01μ g/LNo
Selenium2023-Apr-030.05μ g/LNo
Uranium2023-Apr-030.021μ g/LNo
1st Quarter Nitrite2023-Feb-06<0.05mg/LNo
2nd Quarter Nitrite2023-May-01<0.05mg/LNo
3rd Quarter Nitrite2023-Aug-08<0.05mg/LNo
4th Quarter Nitrite2023-Nov-060.05mg/LNo
1st Quarter Nitrate2023-Feb-060.18mg/LNo
2nd Quarter Nitrate2023-May-01<0.05mg/LNo
3rd Quarter Nitrate2023-Aug-08<0.05mg/LNo
4th Quarter Nitrate2023-Nov-060.05mg/LNo
Sodium2023-Apr-0313.8mg/LNo
ParameterSample Date (YYYY-MM-DD)Result Value (ug/L)Rolling Annual Average Quarter (ug/L)Exceedance
HAA5 1st Quarter2023-Feb-0632.149.4No
HAA5 2nd Quarter2023-May-015.335.9No
HAA5 3rd Quarter2023-Aug-0836.931.1No
HAA5 4th Quarter2023-Nov-0630.726.3No

Notes:

  1. Maximum Allowable Concentration (MAC) for HAA is based on a four-quarter rolling annual average of 0.080 mg/L or 80.0 ug/L

  2. Granular activated carbon (GAC) changed out in all three filters beginning of April

Summary of lead testing under Schedule 15.1 during this reporting period & MDWL #164-<u><strong>101 Issue #6</strong></u> Schedule C, Section 6.6 Range of Lead Results Number of Range of Lead Results Number of

Location TypeNumber of Total SamplesRange of Lead Results 1st One Litre Sample min# – max # (mg/L)Number of Exceedances 1st SampleRange of Lead Results 2nd One Litre Sample min# – max # (mg/L)Number of Exceedances 2nd Sample
Plumbing – residential230.000080 – 0.05970060.000050 – 0.0630006
Plumbing – non residential0N/AN/AN/AN/A
Distribution40.000030 – 0.0009600N/AN/A
Finished Water40.000020 – 0.0000200N/AN/A
Location TypeNumber of Total samplespH (min # - max #)Number of Total samplesTemperature °C (min # - max #)
Plumbing - residential237.12 - 7.83236.7 - 22.1
Plumbing - non residential0N/AN/AN/A
Distribution47.53 - 7.8044.8 - 21.6
Finished Water47.40 - 7.7047.5 - 22.9

Location TypeNumber of Total samplesAlkalinity mg/L (min # - max #)
Plumbing - residential2372 - 105
Plumbing - non-residential0N/A
Distribution473 - 78
Finished Water477 - 97

Notes:

  1. Maximum Allowable Concentration (MAC) for lead is 0.010 mg/L or 10.0 ug/L.

  2. Only Distribution lead samples above 0.010 mg/L or 10.0 ug/L are reportable.

  3. Plumbing samples from residential or non-residential, the occupant receives a letter to indicate if a sample is above the MAC, the results and an information sheet on lead.

Summary of Organic parameters sampled during this reporting period or the <u><strong>most recent sample results</strong></u> Parameter Sample Date Result Unit of Exceedance

ParameterSample Date (YYYY-MM-DD)Result ValueUnit of MeasureExceedance
Alachlor2023-Apr-03<0.02μ g/LNo
Atrazine2023-Apr-03<0.01μ g/LNo
Atrazine + N-dealkylated metabolites2023-Apr-03<0.01μ g/LNo
Azinphos-methyl2023-Apr-03<0.05μ g/LNo
Benzene2023-Apr-03<0.32μ g/LNo
Benzo(a)pyrene2023-Apr-03<0.004μ g/LNo
Bromoxynil2023-Apr-03<0.33μ g/LNo
Carbaryl2023-Apr-03<0.05μ g/LNo
Carbofuran2023-Apr-03<0.01μ g/LNo
Carbon Tetrachloride2023-Apr-03<0.17μ g/LNo
Chlorpyrifos2023-Apr-03<0.02μ g/LNo
Desethyl atrazine2023-Apr-03<0.01μ g/LNo
Diazinon2023-Apr-03<0.02μ g/LNo
Dicamba2023-Apr-03<0.20μ g/LNo
1,2-Dichlorobenzene2023-Apr-03<0.41μ g/LNo
1,4-Dichlorobenzene2023-Apr-03<0.36μ g/LNo
1,1-Dichloroethylene (vinylidene chloride)2023-Apr-03<0.33μ g/LNo
1,2-Dichloroethane2023-Apr-03<0.35μ g/LNo
Dichloromethane2023-Apr-03<0.35μ g/LNo
2,4-Dichlorophenol2023-Apr-03<0.15μ g/LNo
2,4-Dichlorophenoxy acetic acid (2,4-D)2023-Apr-03<0.19μ g/LNo
Diclofop-methyl2023-Apr-03<0.40μ g/LNo
Dimethoate2023-Apr-03<0.06μ g/LNo

Smiths Falls Drinking Water System <u><strong>2023 Annual Report R1</strong></u>

Diquat2023-Apr-03<1μ g/LNo
Diuron2023-Apr-03<0.03μ g/LNo
Glyphosate2023-Apr-03<1μ g/LNo
Malathion2023-Apr-03<0.02μ g/LNo
2-Methyl-4-chlorophenoxyacetic acid (MCPA)2023-Apr-03<0.00012μ g/LNo
Metolachlor2023-Apr-03<0.01μ g/LNo
Metribuzin2023-Apr-03<0.02μ g/LNo
Monochlorobenzene2023-Apr-03<0.3μ g/LNo
Paraquat2023-Apr-03<1μ g/LNo
Pentachlorophenol2023-Apr-03<0.15μ g/LNo
Phorate2023-Apr-03<0.01μ g/LNo
Picloram2023-Apr-03<1μ g/LNo
Polychlorinated Biphenyls (PCB)2023-Apr-03<0.04μ g/LNo
Prometryne2023-Apr-03<0.03μ g/LNo
Simazine2023-Apr-03<0.01μ g/LNo
Terbufos2023-Apr-03<0.01μ g/LNo
Tetrachloroethylene (perchloroethylene)2023-Apr-03<0.35μ g/LNo
2,3,4,6-Tetrachlorophenol2023-Apr-03<0.20μ g/LNo
Triallate2023-Apr-03<0.01μ g/LNo
Trichloroethylene2023-Apr-03<0.44μ g/LNo
2,4,6-Trichlorophenol2023-Apr-03<0.25μ g/LNo
Trifluralin2023-Apr-03<0.02μ g/LNo
Vinyl Chloride2023-Apr-03<0.17μ g/LNo

List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed in Schedule 2 of Ontario Drinking Water Quality Standards. Parameter Result Value Unit of Measure Date of Sample

ParameterResult ValueUnit of MeasureDate of Sample

Glossary

AWQI = adverse water quality indicator

CFU = colony forming units

DWS = drinking water system

DS = distribution system

EA = Environmental Assessment

HAA5 = total haloacetic acid

mg/L = milligrams per liter

MDWL = Municipal Drinking Water License

TTHM = trihalomethane

ug/L = micrograms per liter

WTP = water treatment plant

Contact for more information:

Sarah E. Cooke

Water & Wastewater Compliance Coordinator

Phone: 613-283-4124 ext. 5502

Email: <u>scooke@smithsfalls.ca</u>


Smiths Falls Drinking Water System <u>2023 Annual Report R1</u>

Jason Barlow Manager Water & Wastewater Phone: 613-283-4124 ext. 5501 Email: <u>jbarlow@smithsfalls.ca</u>

O. Reg. 170/03 - Section 11 Annual Reports Page 10 of 10 Revised March 18, 2024 R1