TOWN OF SMITHS FALLS

S

SMITHS FALLS RISE AT THE FALLS

SMITHS FALLS DRINKING WATER SYSTEM 2024 ANNUAL REPORT


Smiths Falls Drinking Water System <u><strong>2024 Annual Report</strong></u>

Drinking-Water System Number:
Drinking-Water System Name: Drinking-Water System Owner: Drinking-Water System Category: Period being reported:

220001307
Smiths Falls Drinking Water System
Corporation of the Town of Smiths Falls
Large Municipal Drinking Water System
January 1st to December 31st, 2024
Complete if your Category is LargeMunicipal Residential or Small MunicipalResidentialDoes your Drinking-Water System serve more than 10,000 people?Yes [ ] No [✓]Is your annual report available to the public at no charge on a web site on the Internet?Yes [✓] No [ ]Location where Annual Report required under O. Reg. 170/03 Schedule 11 will be available to the public.www.smithsfalls.caSmiths Falls Town Hall Complex77 Beckwith St. NSmiths Falls, ON K7A 4T6Complete for all other Categories.Number of Designated Facilities served: N/ADid you provide a copy of your annual report to all Designated Facilities you serve? N/ANumber of Interested Authorities you report to: N/ADid you provide a copy of your annual report to all Interested Authorities you report to for each Designated Facility? N/A

List all Drinking-Water Systems (if any), which receive all of their drinking water from your system:

Drinking Water System NameDrinking Water System Number
Atironto Subdivision – Montague Township260006828

Did you provide a copy of your annual report to all Drinking-Water System owners that are connected to you and to whom you provide all of its drinking water?

Yes [✓] No [ ]

Indicate how you notified system users that your annual report is available, and is free of charge.

[✓] Public access/notice via the web
[ ] Public access/notice via a newspaper


Describe your Drinking-Water System

The Smiths Falls Drinking Water System is comprised of the Water Treatment Plant (WTP) and Distribution system (WDS) which together provides a supply of potable water to the residents and businesses of the Town of Smiths Falls.

The WTP is a Class IV high-rate dissolved air floatation (AquaDAF ®) surface water plant having an approved design capacity of 14,000 m<sup>3</sup>/d with a future expansion to 18,000 m<sup>3</sup>/d. Raw water for the treatment process is drawn from the Rideau River (surface water). The intake structure is located upstream of the WTP approximately 170m. The intake consists of a concrete structure and a 762-millimeter diameter concrete pipe connecting the intake to the diversion chamber where the raw water is directed into the WTP.

Low lift pumps supply water to the AquaDAF ® which is a high-rate dissolved air floatation clarifier. A coagulant & polymer are mixed with the Raw Water to aid in particle removal. Dissolved air will float these particles to form a blanket of sludge which is discharged to the wastewater collection system.

Clarified water flows to 3 granular activate carbon (GAC) & sand filters where further particle removal will take place.

Processes involved include: UV disinfection; chlorination with chlorine gas; corrosion control; fluoridation; chlorine dioxide, residue management and de-chlorination.

The WDS is a Class I subsystem, consisting of 61.94 kilometers (km) of mains, 1096 valves, 332 hydrants and 3010 house services. With a 49.2 meter (m) high water tower that contains 945.75 cubic meters (m<sup>3</sup>) of storage.

List all water treatment chemicals used over this reporting period

CHEMICAL NAMEUSESUPPLIER
PAX-XL6CoagulantKemira
Magnafloc LT22sPolymerNorthland Chemical
Chlorine GasDisinfectionBrenntag
Sodium HydroxideCorrosion ControlBrenntag
Fluorosilicic AcidFluoridePVS Benson
Calcium ThiosulfateDe-chlorinationCleartech
Sodium ChloritePre-treatment Zebra MusselPVS Benson

Were any significant expenses incurred to?

[✓] Install required equipment

[✓] Repair required equipment

[ ] Replace required equipment


Smiths Falls Drinking Water System <u>2024 Annual Report</u>

Please provide a brief description and a breakdown of monetary expenses incurred

S George St re-construction: $514,779.56

S Water tower: $4,717,224.42

S Truck water main for water tower phase 1: $13,147.64

S Overland backfeed system for construction project: $74,496.49

S Analyzer Replacement (AIT-185): $9,411.06

S Filter GAC top up: $17,189.30

S Sludge pump (SLP-162) refurbishment: $8,517.31

S SCADA upgrade: $10,176.00

Provide details on the notices submitted in accordance with subsection 18(1) of the Safe Drinking Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to Spills Action Centre
Incident DateParameterResultUnit of MeasureCorrective ActionCorrective Action Date
2024-May-21 AWQI 164997 Town HallTotal Coliform (TC)5CFU/100mLRe-sample to confirm TC from upstream, down stream (where possible) and site that caused the adverse. Re-enabled post chlorine. Re-sample zero for TC.2024-May-24
2024-May-21 AWQI 164998 Brockville / ArmstrongTotal Coliform (TC)6CFU/100mLRe-sample to confirm TC from upstream, down stream (where possible) and site that caused the adverse. Re-enabled post chlorine. Re-sample zero for TC.2024-May-24
2024-May-21 AWQI 164999 Finished WaterTotal Coliform (TC)2CFU/100mLRe-sample to confirm TC from upstream, down stream (where possible) and site that caused the adverse. Re-enabled post chlorine. Re-sample zero for TC.2024-May-24
2024-Jul-08 AQWI 165486 Power InterruptionOn-site observation, Power failureN/AN/AMCC 2 tripped due to an air condition fault resulting in a portion of the plant power offline. Communication was lost with analyzers and flow meters. Unsure if process were closed at time of power failure. Power restored approximately 15 minutes after lost. Verify processes and production was shutting down. No further actions.2024-Jul-11
2024-Sept-03 AWQI 166197 Union St FlusherTotal Coliform (TC)2CFU/100mLRe-sample to confirm TC from upstream, down stream (where possible) and site that caused the adverse. Re-enabled post chlorine. Re-sample zero for TC.2024-Sept-05
2024-Dec-23 Incident #1-FT6RGPI Potential environmental discharge unchlorinated water to the riverPotential unchlorinated water to the riverN/Amg/LWater Distribution discovered a watermain break bubbling up through the ground on one of the 8" river crossing cast watermains. Location is on shore and is approximately 20 feet from the Rideau River (70 Queen St approximate location 44.895202, -2024-Dec-23

Smiths Falls Drinking Water System <u>2024 Annual Report</u>

76.010011). Appears chlorinated water may have made its way to the Rideau River. Valves on the watermain have been throttled to reduce the flow. Watermain under positive pressure. Emergency locates have been submitted and repairs have commenced around 11:00.

Microbiological testing completed under Schedule 10, 11 or 12 of Regulation 170/03 during this reporting period.

Number of SamplesRange of E. coli Results (min #) - (max #) (CFU/100mL)Range of Total Coliform Results (min #) - (max #) (CFU/100mL)Number of HPC SamplesRange of HPC Results (min #) - (max #) (CFU/100mL)
Raw530 - 510 - 690N/AN/A
Treated540 - 00 - 1*54<10 - 20
Distribution - Routine3250 - 00 - 632510 - 120
Distribution Water main Repairs/new installations/service repairs540 - 00 - 047<10 - 20

Operational testing completed under Schedule 7, 8 or 9 of Regulation 170/03 during the period covered by this Annual Report.

Parameter Tested - (Online Analyzers)Number of Grab SamplesRange of Results MinimumRange of Results AverageRange of Results Maximum
Turbidity - Raw Water (NTU) AIT 102Continuous Monitoring10.0000.89050.000
Turbidity - Raw Water (NTU)(366 bench test)0.3700.9406.570
Turbidity - Filter #1 (NTU) AIT 111Continuous Monitoring20.0000.0305.000
Turbidity - Filter #1 (NTU)(51 bench test)0.0540.1310.255
Turbidity - Filter #2 (NTU) AIT 121Continuous Monitoring20.0000.0325.000
Turbidity - Filter #2 (NTU)(51 bench test)0.0100.1330.218
Turbidity - Filter #3 (NTU) AIT 131Continuous Monitoring20.0000.0325.000
Turbidity - Filter #3 (NTU)(51 bench test)0.0560.1340.257
Turbidity - Finished Water (NTU) AIT 184Continuous Monitoring30.0000.0425.000
Turbidity - Finished Water (NTU)(246 bench test)0.0450.1060.295
Chlorine Total - Zebra Mussel (operation May to October mg/L) AIT 103Continuous Monitoring7 Total ChlorineN/AN/AN/A
Chlorine Total - Zebra Mussel (operation May to October mg/L)(bench test)8N/AN/AN/A
Chlorine Free - Pre-Reservoir (mg/L) AIT 165Continuous Monitoring5 Free Chlorine0.0002.795.000
Chlorine Free - Pre-Reservoir (mg/L)(51 bench test)1.682.523.49
Chlorine Free - Post Reservoir (mg/L) AIT 180Continuous Monitoring5 Free Chlorine0.001.945.00
Chlorine Free - Post Reservoir (mg/L)(51 bench test)1.311.792.28
Chlorine Free - Finished Water (mg/L) AIT 185Continuous Monitoring5 Free Chlorine0.001.932.70
Chlorine Free - Finished Water (mg/L)(246 bench test)1.201.862.47

Smiths Falls Drinking Water System 2024 Annual Report

Chlorine Total - Finished Water (mg/L) AIT 186Continuous Monitoring6 Total Chlorine0.001.802.95
Chlorine Total - Finished Water (mg/L)(246 bench test)1.632.112.81
Fluoride - Finished Water (mg/L) AIT 187Continuous Monitoring40.000.762.00
Fluoride - Finished Water (mg/L)(365 bench test)0.130.560.89
UV Transmittance (%) AIT 160Continuous Monitoring970.095.3100.0
UV Transmittance (%)(239 bench test)82.989.195.7
Notes for above table operational testing completed under Schedule 7, 8 or 9:
  1. High raw water turbidity spikes occur when the low lift pumps (LLP) start and stop, maintenance, calibration and flushing of lines.

  2. High filter turbidity results of filter backwash, process upset or calibration.

  3. High finished water turbidity results of high lift pumps (HLP) starting or calibration.

  4. High fluoride readings occur on HLP starts, maintenance or calibration while chemical system was off.

  5. Low free chlorine residual (pre-reservoir, post reservoir and finished water) result of generator backup power testing, maintenance or calibration.

  6. Low total chlorine residual (finished water) result of generator backup power testing, maintenance or calibration.

  7. High total chlorine residuals (for zebra mussel control) can be due the sampling alternates between intake and LLP header.

  8. Bench tests for total chlorine (zebra mussel) are sampled from the raw water stainless steel sample tap located in pump gallery or raw water sample tap in lab

  9. Low UV transmittance result of generator backup power testing, maintenance, calibration or Optiview failure.

Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument.

Date of legal instrument issuedParameterDate Sampled (YYYY-MM-DD)Result (μ g/L)Quarterly Average (μ g/L)Rolling Annual Average Quarter (μ g/L)
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-Jan-0253.044.742.8
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-Feb-0531.044.742.8
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-Mar-0450.044.742.8
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-Apr-0263.076.053.8
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-May-0674.076.053.8
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-Jun-0391.076.053.8
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-Jul-02108.0108.067.4
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-Aug-03121.0108.067.4
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-Sept-0395.0108.067.4
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-Oct-0783.071.074.9
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-Nov-0475.071.074.9
Municipal Drinking Water License #164-101 Issue #7 (Schedule C section 5 table 5)TTHM2024-Dec-0255.071.074.9
Notes:
  1. Maximum Allowable Concentration (MAC) for THM is based on a four-quarter rolling annual average of 0.100 mg/L or 100.0 ug/L

Smiths Falls Drinking Water System <u><strong>2024 Annual Report</strong></u>

Date of legal instrument issuedParameterDate Sampled (YYYY-MM-DD)Result -Monthly TSS Average (mg/L)Result -Monthly Grab Average Total Chlorine (mg/L)
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-Jan-096.300.01
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-Feb-125.130.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-Mar-116.870.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-Apr-152.370.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-May-144.400.01
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-Jun-283.570.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-Jul-173.470.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-Aug-292.130.03
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-Sept-094.370.06
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-Oct-185.630.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-Nov-253.600.02
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)2024-Dec-205.530.01
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)TSS (grab sample)Annual average4.450.02
Date of legal instrument issuedParameterSample Date (YYYY-MM-DD)Result Value (mg/L)Exceedance
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorite2024-Sept-030.01No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorite2024-Nov-040.08No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorate2024-Sept-030.11No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 1.5 table 3)Chlorate2024-Nov-040.14No

Note: MDWL revised July 2024 to include above noted sampling also took time to procure the testing equipment for sparging.

Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument.

Date of legal instrument issuedParameterSample Date (YYYY-MM-DD)Result Value (μ g/L)Exceedance
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 6)Microcystin2024-Jun-06<0.1No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 6)Microcystin2024-Jul-05<0.1No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 6)Microcystin2024-Aug-09<0.1No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 6)Microcystin2024-Sept-03<0.1No
Municipal Drinking Water License #164-101 issue #7 (Schedule C section 6)Microcystin2024-Oct-09<0.1No

Smiths Falls Drinking Water System <u><strong>2024 Annual Report</strong></u>

Summary of Inorganic parameters tested during this reporting period or the most recent sample results Parameter Sample Date Result Value Unit of Exceedance

ParameterSample Date (YYYY-MM-DD)Result ValueUnit of MeasureExceedance
Antimony2024-Apr-02<0.6μ g/LNo
Arsenic2024-Apr-02<0.2μ g/LNo
Barium2024-Apr-0245.6μ g/LNo
Boron2024-Apr-0213μ g/LNo
Cadmium2024-Apr-020.005μ g/LNo
Chromium2024-Apr-020.25μ g/LNo
Mercury2024-Apr-02<0.01μ g/LNo
Selenium2024-Apr-020.08μ g/LNo
Uranium2024-Apr-020.008μ g/LNo
1st Quarter Nitrite2024-Feb-05<0.05mg/LNo
2nd Quarter Nitrite2024-May-06<0.05mg/LNo
3rd Quarter Nitrite2024-Aug-06<0.05mg/LNo
4th Quarter Nitrite2024-Nov-04<0.05mg/LNo
1st Quarter Nitrate2024-Feb-050.19mg/LNo
2nd Quarter Nitrate2024-May-060.10mg/LNo
3rd Quarter Nitrate2024-Aug-060.12mg/LNo
4th Quarter Nitrate2024-Nov-04<0.05mg/LNo
Sodium2024-Apr-0216.4mg/LNo
ParameterSample Date (YYYY-MM-DD)Result Value (ug/L)Rolling Annual Average Quarter (ug/L)Exceedance
HAA5 1st Quarter2024-Feb-0530.725.9No
HAA5 2nd Quarter2024-May-0660.439.7No
HAA5 3rd Quarter2024-Aug-0658.944.1No
HAA5 4th Quarter2024-Nov-0442.648.2No
Notes:
  1. Maximum Allowable Concentration (MAC) for HAA is based on a four-quarter rolling annual average of 0.080 mg/L or 80.0 ug/L

  2. Granular activated carbon (GAC) changed out in all three filters beginning of April


Smiths Falls Drinking Water System <u><strong>2024 Annual Report</strong></u>

Summary of lead testing under Schedule 15.1 during this reporting period & MDWL #164-<u><strong>101 Issue #6</strong></u> Schedule C, Section 6.6 Range of Lead Results Number of Range of Lead Results Number of

Location TypeNumber of Total SamplesRange of Lead Results 1st One Litre Sample min# - max # (mg/L)Number of Exceedances 1st SampleRange of Lead Results 2nd One Litre Sample min# - max # (mg/L)Number of Exceedances 2nd Sample
Plumbing - residential200.000100 - 0.02050070.000080 - 0.0278008
Plumbing - non residential20.000090 - 0.02920010.000060 - 0.0813001
Distribution40.000020 - 0.0001100N/AN/A
Finished Water40.000020 - 0.0000200N/AN/A
Location TypeNumber of Total samplespH (min # - max #)Number of Total samplesTemperature °C (min # - max #)
Plumbing - residential207.38 -7.772011.7 - 40.4
Plumbing - non residential27.65 - 7.74213.0 -23.7
Distribution47.57 - 7.7445.6 - 20.8
Finished Water47.41 - 7.7947.5 - 23.6
Location TypeNumber of Total samplesAlkalinity mg/L (min # - max #)
Plumbing - residential2079 - 107
Plumbing - non-residential290 - 96
Distribution492 - 99
Finished Water488 - 98

Notes:

  1. Maximum Allowable Concentration (MAC) for lead is 0.010 mg/L or 10.0 ug/L.

  2. Finished water and Distribution lead samples above 0.010 mg/L or 10.0 ug/L are reportable to SAC and Health Unit.

  3. Plumbing samples from residential or non-residential, the occupant receives a letter to indicate if a sample is above the MAC, the results and an information sheet on lead.


Summary of Organic parameters sampled during this reporting period or the <u><strong>most recent sample results</strong></u> Parameter Sample Date Result Unit of Exceedance

ParameterSample Date (YYYY-MM-DD)Result ValueUnit of MeasureExceedance
Alachlor2024-Apr-02<0.02μ g/LNo
Atrazine2024-Apr-02<0.01μ g/LNo
Atrazine + N-dealkylated metabolites2024-Apr-02<0.01μ g/LNo
Azinphos-methyl2024-Apr-02<0.05μ g/LNo
Benzene2024-Apr-02<0.32μ g/LNo
Benzo(a)pyrene2024-Apr-02<0.04μ g/LNo
Bromoxynil2024-Apr-02<0.33μ g/LNo
Carbaryl2024-Apr-02<0.05μ g/LNo
Carbofuran2024-Apr-02<0.01μ g/LNo
Carbon Tetrachloride2024-Apr-02<0.17μ g/LNo
Chlorpyrifos2024-Apr-02<0.02μ g/LNo
Desethyl atrazine2024-Apr-02<0.01μ g/LNo
Diazinon2024-Apr-02<0.02μ g/LNo
Dicamba2024-Apr-02<0.20μ g/LNo
1,2-Dichlorobenzene2024-Apr-02<0.41μ g/LNo
1,4-Dichlorobenzene2024-Apr-02<0.36μ g/LNo
1,1-Dichloroethylene (vinylidene chloride)2024-Apr-02<0.33μ g/LNo
1,2-Dichloroethane2024-Apr-02<0.35μ g/LNo
Dichloromethane2024-Apr-02<0.35μ g/LNo
2,4-Dichlorophenol2024-Apr-02<0.15μ g/LNo
2,4-Dichlorophenoxy acetic acid (2,4-D)2024-Apr-02<0.19μ g/LNo
Diclofop-methyl2024-Apr-02<0.40μ g/LNo
Dimethoate2024-Apr-02<0.06μ g/LNo
Diquat2024-Apr-02<1μ g/LNo
Diuron2024-Apr-02<0.03μ g/LNo
Glyphosate2024-Apr-02<1μ g/LNo
Malathion2024-Apr-02<0.02μ g/LNo
2-Methyl-4-chlorophenoxyacetic acid (MCPA)2024-Apr-02<0.00012μ g/LNo
Metolachlor2024-Apr-02<0.01μ g/LNo
Metribuzin2024-Apr-02<0.02μ g/LNo
Monochlorobenzene2024-Apr-02<0.3μ g/LNo
Paraquat2024-Apr-02<1μ g/LNo
Pentachlorophenol2024-Apr-02<0.15μ g/LNo
Phorate2024-Apr-02<0.01μ g/LNo
Picloram2024-Apr-02<1μ g/LNo
Polychlorinated Biphenyls (PCB)2024-Apr-02<0.04μ g/LNo
Prometryne2024-Apr-02<0.03μ g/LNo
Simazine2024-Apr-02<0.01μ g/LNo
Terbufos2024-Apr-02<0.01μ g/LNo
Tetrachloroethylene (perchloroethylene)2024-Apr-02<0.35μ g/LNo
2,3,4,6-Tetrachlorophenol2024-Apr-02<20.0μ g/LNo
Triallate2024-Apr-02<0.1μ g/LNo
Trichloroethylene2024-Apr-02<0.44μ g/LNo
2,4,6-Trichlorophenol2024-Apr-02<0.25μ g/LNo
Trifluralin2024-Apr-02<0.02μ g/LNo
Vinyl Chloride2024-Apr-02<0.17μ g/LNo

Smiths Falls Drinking Water System <u><strong>2024 Annual Report</strong></u>

List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed in Schedule 2 of Ontario Drinking Water Quality Standards. Parameter Result Value Unit of Measure Date of Sample

ParameterResult ValueUnit of MeasureDate of Sample

Glossary

AWQI = adverse water quality indicator

CFU = colony forming units

DWS = drinking water system

DS = distribution system

EA = Environmental Assessment

HAA5 = total haloacetic acid

mg/L = milligrams per liter

MDWL = Municipal Drinking Water License

TTHM = trihalomethane

ug/L = micrograms per liter

WTP = water treatment plant

Contact for more information:

Sarah E. Cooke

Water & Wastewater Compliance Coordinator

Phone: 613-283-4124 ext. 5502

Email: <u>scooke@smithsfalls.ca</u>

Andrew MacNaughton

Manager Water/Wastewater Treatment

Phone: 613-283-4124 ext. 5501

Email: <u>amacnaughton@smithsfalls.ca</u>